EXPECTED OUTCOME (offline simulation, no PLCSIM) - BPS-1 program v1.0

Generated 2026-11-22 18:16:26 UTC by TAIPilot
NOT PASSED

1. Identification

ProjectTAIPilotDemo_BPS1
PLC / CPUPLC_BPS1 / CPU 1511-1 PN
DB_Info.ProgramBPS-1
DB_Info.ProgVersionv1.0
PLCSIM instanceoffline: Bps1Sim (C# port of demo/plc, v1.0 with 3 defects)
SuiteBPS-1 booster pump station - FAT on PLCSIM with plant model (bps1_suite.json)
Suite SHA-256715e4d1109ce1d455b31ff39ad3ee6bc1bcadb4bbd721b574d91d2f542805138
Runoffline-v1.0 (completed)
Run date (UTC)2026-11-22 00:00:00 - 2026-11-22 00:00:00
Executioncycle, 100 ms virtual time per cycle; 0 s wall clock in 1 call(s)
Selectionall tests
TAIPilot versionoffline simulation (Bps1Sim, no PLCSIM)

2. Summary

23tests
17Passed
4Failed
1Expected fail (known deviation)
1Not applicable

Requirements: 35, without tests: 0, failing: 6.

Notes: Offline simulation: the PLC is the C# test double Bps1Sim, not S7-PLCSIM Advanced.

3. Tests

#TestRequirementsResultDuration (PLC time)
1T01_ModeOff_AllOutputsOff
Mode Off switches every pump and valve output off
Note: plant model: 264 steps, tag I/O 10 ms in 1320 read + 363 write calls, model 9 ms; model events: 0 s set tank.initial_level_m = 3.6; 0 s set tank.initial_level_m = 1.4
BPS-3.1-R01, BPS-3.1-R02PASS
15 steps, 0 failed
26.1 s
wall 0 ms
2T02_Manual_PumpsIndividually
Mode Manual: each pump is started and stopped by the operator and runs at the manual speed
Note: plant model: 47 steps, tag I/O 0 ms in 235 read + 30 write calls, model 1 ms; model events: 0 s set tank.initial_level_m = 3.6; 0 s set tank.initial_level_m = 2
BPS-3.1-R01, BPS-3.2-R01PASS
18 steps, 0 failed
4.4 s
wall 0 ms
3T03_Manual_ProtectionsActive
Mode Manual: high pressure trip and emergency stop still stop the pump
Note: plant model: 72 steps, tag I/O 0 ms in 360 read + 85 write calls, model 2 ms; model events: 0 s set tank.initial_level_m = 3.6; 0.1 s set tank.initial_level_m = 2; 6.2 s fault PT201: offset 7 (engineering units); 6.3 s fault PT201: cleared; 6.4 s fault forced ESTOP_OK = 0; 6.5 s fault released ESTOP_OK
BPS-3.2-R02PASS
18 steps, 0 failed
6.5 s
wall 0 ms
4T04_EStop_StopsAll_RestartAfterAck
Emergency stop: pumps stop and the inlet valve closes at once; restart only after acknowledge
Note: plant model: 234 steps, tag I/O 1 ms in 1170 read + 375 write calls, model 6 ms; model events: 0 s set tank.initial_level_m = 3.6; 0 s set tank.initial_level_m = 1.4; 16.1 s fault forced ESTOP_OK = 0; 16.2 s fault released ESTOP_OK
BPS-3.3-R01, BPS-3.3-R02PASS
19 steps, 0 failed
22.9 s
wall 0 ms
5T05_Refill_Hysteresis
Inlet valve opens below 40 %, stays open in between, closes above 85 %
Note: plant model: 689 steps, tag I/O 2 ms in 3445 read + 870 write calls, model 22 ms; model events: 0 s set tank.initial_level_m = 3.6; 0.1 s set tank.initial_level_m = 2; 19.1 s set tank.initial_level_m = 1.5; 24.2 s set tank.initial_level_m = 3; 27.2 s set tank.initial_level_m = 3.36
BPS-4.1-R01, BPS-4.1-R02PASS
20 steps, 0 failed
1 min 08 s
wall 0 ms
6T06_HighLevel_ValveStuckOpen
Inlet valve stuck open: valve alarm, then high level alarm with the valve commanded closed
Note: plant model: 1281 steps, tag I/O 5 ms in 6405 read + 1539 write calls, model 41 ms; model events: 0 s set tank.initial_level_m = 3.6; 0 s set tank.initial_level_m = 3.7; 16 s fault XV101: stuck at 100 %; 127.6 s fault XV101: cleared
BPS-4.2-R01, BPS-4.3-R01PASS
18 steps, 0 failed
2 min 08 s
wall 0 ms
7T07_MainsPressureSwitch
Optional mains pressure switch PS-100 raises A_MainsLow
Not applicable: BPS-1 is built without the optional mains pressure switch PS-100 (A_MainsLow is held FALSE).
BPS-4.4-R01N/A
8T08_DryRun_StopAndRestartHysteresis
Dry-run protection: pumps stop below 10 % and restart only above 20 %
Note: plant model: 719 steps, tag I/O 2 ms in 3595 read + 1006 write calls, model 21 ms; model events: 0 s set tank.initial_level_m = 3.6; 0 s set tank.initial_level_m = 0.48; 16.1 s set inlet_flow.factor = 0; 70.9 s set inlet_flow.factor = 0.2
StepTagExpectedObserved
#15 Pumps stay off while the level is between 10 % and 20 %P1_RunFALSE1 (value 1 at 500 ms is not FALSE)
BPS-5.1-R01, BPS-5.1-R02FAIL
15 steps, 1 failed
1 min 11 s
wall 0 ms
9T09_LevelTransmitterFault
Level transmitter wire break: alarm, pumps stop, inlet valve closes
Note: plant model: 169 steps, tag I/O 1 ms in 845 read + 239 write calls, model 6 ms; model events: 0 s set tank.initial_level_m = 3.6; 0.1 s set tank.initial_level_m = 1.4; 16.2 s fault LT101: open_circuit; 16.3 s fault LT101: cleared
BPS-5.2-R01PASS
18 steps, 0 failed
16.4 s
wall 0 ms
10T10_PressureControl_SteadyState
PI pressure control: 4.0 bar +/- 0.2 bar at constant consumption, one duty pump
Note: plant model: 964 steps, tag I/O 3 ms in 4820 read + 1377 write calls, model 36 ms; model events: 0 s set tank.initial_level_m = 3.6; 0.1 s set tank.initial_level_m = 2
BPS-6.1-R01, BPS-6.1-R02, BPS-8.1-R01PASS
14 steps, 0 failed
1 min 36 s
wall 0 ms
11T11_ControllerOutputLimits
Controller output stays between the minimum speed (30 %) and 100 %
Note: plant model: 491 steps, tag I/O 1 ms in 2455 read + 614 write calls, model 11 ms; model events: 0 s set tank.initial_level_m = 3.6; 0 s set tank.initial_level_m = 2; 16 s set demand.value = 0; 39.9 s set demand.value = 30
BPS-6.1-R03PASS
19 steps, 0 failed
48.6 s
wall 0 ms
12T12_ConsumptionStep_PressureDeviation
Consumption step 12 -> 30 m3/h: pressure within 0.3 bar of the setpoint
Expected to fail: Known deviation: one pump delivers ~20 m3/h at 4 bar and the assist pump may start only after the 10 s assist delay of 8.2, so the pressure dips to ~2.6 bar for about 10 s. Accepted for BPS-1; spec 6.2 to be revised.
Note: plant model: 169 steps, tag I/O 1 ms in 845 read + 282 write calls, model 7 ms; model events: 0 s set tank.initial_level_m = 3.6; 0 s set tank.initial_level_m = 2; 16.1 s set demand.value = 30
StepTagExpectedObserved
#13 Header pressure within 0.3 bar of the setpoint for 60 sDB_Station.Pressure_bar{"min":3.7,"max":4.3}3.5366 (value 3.5366 at 400 ms is not in [3.7, 4.3])
BPS-6.2-R01XFAIL
13 steps, 1 failed
16.5 s
wall 0 ms
13T13_PressureTransmitterFault_Fallback
Pressure transmitter wire break: alarm, pumps continue at the fallback speed 70 %
Note: plant model: 316 steps, tag I/O 1 ms in 1580 read + 459 write calls, model 11 ms; model events: 0 s set tank.initial_level_m = 3.6; 0 s set tank.initial_level_m = 2; 16 s fault PT201: open_circuit; 26.1 s fault PT201: cleared
BPS-6.3-R01PASS
18 steps, 0 failed
31.1 s
wall 0 ms
14T14_HighPressureTrip_LatchedUntilAck
High pressure trip stops all pumps and stays active until acknowledged; lamp H-001
Note: plant model: 263 steps, tag I/O 1 ms in 1315 read + 371 write calls, model 6 ms; model events: 0 s set tank.initial_level_m = 3.6; 0 s set tank.initial_level_m = 2; 16 s fault PT201: offset 7 (engineering units); 19.1 s fault PT201: cleared
BPS-7.1-R01, BPS-7.1-R02, BPS-10-R01, BPS-10-R02PASS
20 steps, 0 failed
25.8 s
wall 0 ms
15T15_LowPressureWarning
Pipe burst: A_LowPressure after 10 s below 2.0 bar, pumps keep running
Note: plant model: 275 steps, tag I/O 1 ms in 1375 read + 464 write calls, model 11 ms; model events: 0 s set tank.initial_level_m = 3.6; 0 s set tank.initial_level_m = 2; 16 s fault hdr: burst 80 m3/h; 27 s fault hdr: cleared
BPS-7.2-R01PASS
17 steps, 0 failed
27.0 s
wall 0 ms
16T16_DutySelection_LowerRunHours[lower=1]
Station start: P-101 has the lower run hours and becomes the duty pump
Note: plant model: 24 steps, tag I/O 0 ms in 120 read + 9 write calls, model 0 ms; model events: 0 s set tank.initial_level_m = 3.6; 0 s set tank.initial_level_m = 2
StepTagExpectedObserved
#12 P-101 is the duty pump (after 1.0 s)P1_RunTRUEFALSE
DB_Station.DutyPump12
BPS-8.1-R01, BPS-8.1-R02FAIL
12 steps, 1 failed
2.1 s
wall 0 ms
17T16_DutySelection_LowerRunHours[lower=2]
Station start: P-102 has the lower run hours and becomes the duty pump
Note: plant model: 23 steps, tag I/O 0 ms in 115 read + 9 write calls, model 0 ms; model events: 0 s set tank.initial_level_m = 3.6; 0 s set tank.initial_level_m = 2
StepTagExpectedObserved
#12 P-102 is the duty pump (after 1.0 s)P2_RunTRUEFALSE
DB_Station.DutyPump21
BPS-8.1-R01, BPS-8.1-R02FAIL
12 steps, 1 failed
2.0 s
wall 0 ms
18T17_DutyAlternation
Duty pump changes over after the alternation time (60 s in the test)
Note: plant model: 615 steps, tag I/O 2 ms in 3075 read + 911 write calls, model 23 ms; model events: 0 s set tank.initial_level_m = 3.6; 0 s set tank.initial_level_m = 2
BPS-8.1-R03PASS
14 steps, 0 failed
1 min 01 s
wall 0 ms
19T18_AssistPump
Assist pump starts after 10 s at 100 % speed and stops below 80 % speed
Note: plant model: 488 steps, tag I/O 1 ms in 2440 read + 846 write calls, model 17 ms; model events: 0 s set tank.initial_level_m = 3.6; 0 s set tank.initial_level_m = 2; 16 s set demand.value = 30; 31.6 s set demand.value = 12
BPS-8.2-R01, BPS-8.2-R02PASS
19 steps, 0 failed
48.3 s
wall 0 ms
20T19_FeedbackLoss_Failover
Duty pump loses its running feedback: A_P1_NoFeedback after 5 s, P-102 takes over within 2 s
Note: plant model: 235 steps, tag I/O 1 ms in 1175 read + 350 write calls, model 7 ms; model events: 0 s set tank.initial_level_m = 3.6; 0 s set tank.initial_level_m = 2; 16 s fault P1_fb: never_confirms
StepTagExpectedObserved
#15 Standby P-102 takes over within 2 s (after 2.0 s)P2_RunTRUEFALSE
DB_Station.DutyPump21
BPS-8.3-R01, BPS-8.3-R02FAIL
15 steps, 1 failed
23.1 s
wall 0 ms
21T20_VfdFault
VFD fault stops the pump and raises A_P1_VfdFault
Note: plant model: 170 steps, tag I/O 0 ms in 850 read + 282 write calls, model 5 ms; model events: 0 s set tank.initial_level_m = 3.6; 0 s set tank.initial_level_m = 2; 16.2 s fault forced P1_VfdFault = 1; 16.4 s fault released P1_VfdFault
BPS-8.3-R03PASS
16 steps, 0 failed
16.5 s
wall 0 ms
22T21_RunHoursAndStarts
Run hours and starts are counted per pump
Note: plant model: 3656 steps, tag I/O 11 ms in 18280 read + 4693 write calls, model 119 ms; model events: 0 s set tank.initial_level_m = 3.6; 0 s set tank.initial_level_m = 2
BPS-8.4-R01PASS
18 steps, 0 failed
6 min 05 s
wall 0 ms
23T22_SetpointSets
Setpoint sets Night and Maintenance are loaded without stopping the pumps
Note: plant model: 379 steps, tag I/O 1 ms in 1895 read + 684 write calls, model 12 ms; model events: 0 s set tank.initial_level_m = 3.6; 0.1 s set tank.initial_level_m = 2
BPS-9-R01, BPS-9-R02PASS
18 steps, 0 failed
37.6 s
wall 0 ms

3.1 Trajectories

Recorded PLC tags and plant-model signals over PLC (virtual) time. Shaded: assertion windows (green passed, red failed); dashed: expect_range bounds; red ring / line: first violation. Data: one CSV per test next to this report.

T01_ModeOff_AllOutputsOff — PASS Mode Off switches every pump and valve output off · 55 samples every 500 ms of PLC time #3 Setup: pumps stopped, valve closed, Day set active #1 #7 Setup: no alarm left #2 #9 Setup: duty pump P-101 confirms running #3 #10 Setup: header pressure at the setpoint #4 #12 Auto at 35 % level: duty pump runs and the inlet valve refills #5 #14 All outputs off within 0.5 s #6 #15 They stay off #7 DB_Station.Pressure_bar DB_Station.Speed_pct model:tank.level_pct model:demand_m3h 0 20 40 60 80 100 DB_Station.Pressure_bar DB_Station.Speed_pct model:tank.level_pct model:demand_m3h P1_RunP1_Run P2_RunP2_Run XV101_OpenXV101_Open H001_AlarmLampH001_AlarmLamp 0 5 10 15 20 25 PLC time (virtual), s
T01_ModeOff_AllOutputsOff: P1_Run, P2_Run, XV101_Open, H001_AlarmLamp, DB_Station.Pressure_bar, DB_Station.Speed_pct, model:tank.level_pct, model:demand_m3h — CSV, SHA-256 56576cfe21f25deabcaaa993112f6f187249318c8250ecd818fd21ff94cde309
T02_Manual_PumpsIndividually — PASS Mode Manual: each pump is started and stopped by the operator and runs at the manual speed · 13 samples every 500 ms of PLC time #3 Setup: pumps stopped, valve closed, Day set active #1 #7 Setup: no alarm left #2 #9 Nothing runs without a manual command #3 #11 Only P-102 runs, at the manual speed 80 % #4 #12 P-101 stays off #5 #14 Both pumps run #6 #16 Only P-101 runs #7 #18 No pump runs #8 DB_Station.Pressure_bar DB_Station.Speed_pct model:tank.level_pct model:demand_m3h 0 20 40 60 80 DB_Station.Pressure_bar DB_Station.Speed_pct model:tank.level_pct model:demand_m3h P1_RunP1_Run P2_RunP2_Run XV101_OpenXV101_Open H001_AlarmLampH001_AlarmLamp 0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 PLC time (virtual), s
T02_Manual_PumpsIndividually: P1_Run, P2_Run, XV101_Open, H001_AlarmLamp, DB_Station.Pressure_bar, DB_Station.Speed_pct, model:tank.level_pct, model:demand_m3h — CSV, SHA-256 588385043f4e4a1b5b1ddd2ce8d4b7ceb9caa570c74090e36f4a84b282bd2859
T03_Manual_ProtectionsActive — PASS Mode Manual: high pressure trip and emergency stop still stop the pump · 18 samples every 500 ms of PLC time #3 Setup: pumps stopped, valve closed, Day set active #1 #7 Setup: no alarm left #2 #10 P-101 runs #3 #12 High pressure trip stops P-101 in mode Manual #4 #15 P-101 restarts (manual command still on) #5 #17 Emergency stop stops P-101 in mode Manual #6 DB_Station.Pressure_bar DB_Station.Speed_pct model:tank.level_pct model:demand_m3h 0 20 40 60 80 DB_Station.Pressure_bar DB_Station.Speed_pct model:tank.level_pct model:demand_m3h P1_RunP1_Run P2_RunP2_Run XV101_OpenXV101_Open H001_AlarmLampH001_AlarmLamp 0 1 2 3 4 5 6 PLC time (virtual), s
T03_Manual_ProtectionsActive: P1_Run, P2_Run, XV101_Open, H001_AlarmLamp, DB_Station.Pressure_bar, DB_Station.Speed_pct, model:tank.level_pct, model:demand_m3h — CSV, SHA-256 c334bd9eff2305d3626ef546692893d50f76fbe2bba82f79642a6dac2cecff76
T04_EStop_StopsAll_RestartAfterAck — PASS Emergency stop: pumps stop and the inlet valve closes at once; restart only after acknowledge · 51 samples every 500 ms of PLC time #3 Setup: pumps stopped, valve closed, Day set active #1 #7 Setup: no alarm left #2 #9 Setup: duty pump P-101 confirms running #3 #10 Setup: header pressure at the setpoint #4 #12 Duty pump runs, inlet valve open #5 #14 Pumps off and valve closed within 0.5 s #6 #16 No restart without acknowledge #7 #18 Station restarts after the acknowledge #8 #19 One pump running again #9 DB_Station.Pressure_bar DB_Station.Speed_pct model:tank.level_pct model:demand_m3h 0 20 40 60 80 100 DB_Station.Pressure_bar DB_Station.Speed_pct model:tank.level_pct model:demand_m3h P1_RunP1_Run P2_RunP2_Run XV101_OpenXV101_Open H001_AlarmLampH001_AlarmLamp 0 2 4 6 8 10 12 14 16 18 20 22 PLC time (virtual), s
T04_EStop_StopsAll_RestartAfterAck: P1_Run, P2_Run, XV101_Open, H001_AlarmLamp, DB_Station.Pressure_bar, DB_Station.Speed_pct, model:tank.level_pct, model:demand_m3h — CSV, SHA-256 46645045f911b97316d95fe91f317e0bfd1ab9ed5fce100404a8854f71d57ef0
T05_Refill_Hysteresis — PASS Inlet valve opens below 40 %, stays open in between, closes above 85 % · 141 samples every 500 ms of PLC time #3 Setup: pumps stopped, valve closed, Day set active #1 #7 Setup: no alarm left #2 #9 Setup: duty pump P-101 confirms running #3 #10 Setup: header pressure at the setpoint #4 #12 50 % after a high level: valve stays closed (hysteresis) #5 #14 Valve opens below the refill start level #6 #15 Open limit switch from the model (5 s travel) #7 #17 Valve stays open between the start and the stop level #8 #19 Valve closes when the level rises above 85 % #9 #20 Closed limit switch #10 DB_Station.Pressure_bar DB_Station.Speed_pct model:tank.level_pct model:demand_m3h 0 20 40 60 80 100 DB_Station.Pressure_bar DB_Station.Speed_pct model:tank.level_pct model:demand_m3h P1_RunP1_Run P2_RunP2_Run XV101_OpenXV101_Open H001_AlarmLampH001_AlarmLamp 0 10 20 30 40 50 60 PLC time (virtual), s
T05_Refill_Hysteresis: P1_Run, P2_Run, XV101_Open, H001_AlarmLamp, DB_Station.Pressure_bar, DB_Station.Speed_pct, model:tank.level_pct, model:demand_m3h — CSV, SHA-256 5f6a35425c53639c8a538748383ad0691803cb6c0e3551e4796e6f7a4e6e4c27
T06_HighLevel_ValveStuckOpen — PASS Inlet valve stuck open: valve alarm, then high level alarm with the valve commanded closed · 258 samples every 500 ms of PLC time #3 Setup: pumps stopped, valve closed, Day set active #1 #7 Setup: no alarm left #2 #9 Setup: duty pump P-101 confirms running #3 #10 Setup: header pressure at the setpoint #4 #12 92.5 %: valve commanded closed #5 #14 No valve alarm before 15 s #6 #15 A_ValveFault: closed position not reached #7 #16 The tank overfills: A_HighLevel above 95 %, valve still commanded closed #8 #17 Common alarm lamp #9 DB_Station.Pressure_bar DB_Station.Speed_pct model:tank.level_pct model:demand_m3h 0 20 40 60 80 100 DB_Station.Pressure_bar DB_Station.Speed_pct model:tank.level_pct model:demand_m3h P1_RunP1_Run P2_RunP2_Run XV101_OpenXV101_Open H001_AlarmLampH001_AlarmLamp 0 20 40 60 80 100 120 PLC time (virtual), s
T06_HighLevel_ValveStuckOpen: P1_Run, P2_Run, XV101_Open, H001_AlarmLamp, DB_Station.Pressure_bar, DB_Station.Speed_pct, model:tank.level_pct, model:demand_m3h — CSV, SHA-256 7d097571316caab8c7b6c001b4452384a7078866356c9eba45446c074267a97c
T08_DryRun_StopAndRestartHysteresis — FAIL Dry-run protection: pumps stop below 10 % and restart only above 20 % · 146 samples every 500 ms of PLC time #3 Setup: pumps stopped, valve closed, Day set active #1 #7 Setup: no alarm left #2 #9 Setup: duty pump P-101 confirms running #3 #10 Setup: header pressure at the setpoint #4 #13 Pumps stop as soon as the level falls below 10 %, A_LowLevel #5 #15 Pumps stay off while the level is between 10 % and 20 % #6 DB_Station.Pressure_bar DB_Station.Speed_pct model:tank.level_pct model:demand_m3h 0 20 40 60 80 100 DB_Station.Pressure_bar DB_Station.Speed_pct model:tank.level_pct model:demand_m3h P1_RunP1_Run P2_RunP2_Run XV101_OpenXV101_Open H001_AlarmLampH001_AlarmLamp #15 Pumps stay off while the level is between 10 % and 20 % failed at 1.19 min 0 10 20 30 40 50 60 70 PLC time (virtual), s
T08_DryRun_StopAndRestartHysteresis: P1_Run, P2_Run, XV101_Open, H001_AlarmLamp, DB_Station.Pressure_bar, DB_Station.Speed_pct, model:tank.level_pct, model:demand_m3h — CSV, SHA-256 0c42fed652afcf89dd0412b602a7c97e11190b1cc28af2ab83e0c6c03c187ab0
T09_LevelTransmitterFault — PASS Level transmitter wire break: alarm, pumps stop, inlet valve closes · 38 samples every 500 ms of PLC time #3 Setup: pumps stopped, valve closed, Day set active #1 #7 Setup: no alarm left #2 #9 Setup: duty pump P-101 confirms running #3 #10 Setup: header pressure at the setpoint #4 #12 Duty pump runs, valve open #5 #14 A_LevelSensor, pumps off, valve closed #6 #17 Station runs again #7 #18 One pump running again #8 DB_Station.Pressure_bar DB_Station.Speed_pct model:tank.level_pct model:demand_m3h 0 20 40 60 80 100 DB_Station.Pressure_bar DB_Station.Speed_pct model:tank.level_pct model:demand_m3h P1_RunP1_Run P2_RunP2_Run XV101_OpenXV101_Open H001_AlarmLampH001_AlarmLamp 0 2 4 6 8 10 12 14 16 PLC time (virtual), s
T09_LevelTransmitterFault: P1_Run, P2_Run, XV101_Open, H001_AlarmLamp, DB_Station.Pressure_bar, DB_Station.Speed_pct, model:tank.level_pct, model:demand_m3h — CSV, SHA-256 c474dc424857e0d4abff50ab65aeb1ec0f19743c5bf79a7faa45d38f8464ed30
T10_PressureControl_SteadyState — PASS PI pressure control: 4.0 bar +/- 0.2 bar at constant consumption, one duty pump · 195 samples every 500 ms of PLC time #3 Setup: pumps stopped, valve closed, Day set active #1 #7 Setup: no alarm left #2 #9 Setup: duty pump P-101 confirms running #3 #10 Setup: header pressure at the setpoint #4 #12 Header pressure within 0.2 bar of the setpoint for 60 s #5 #13 One duty pump, the other on standby #6 #14 Pressure no longer drifts #7 DB_Station.Pressure_bar DB_Station.Speed_pct model:tank.level_pct model:demand_m3h 0 20 40 60 80 100 DB_Station.Pressure_bar DB_Station.Speed_pct model:tank.level_pct model:demand_m3h P1_RunP1_Run P2_RunP2_Run XV101_OpenXV101_Open H001_AlarmLampH001_AlarmLamp 0 10 20 30 40 50 60 70 80 90 PLC time (virtual), s
T10_PressureControl_SteadyState: P1_Run, P2_Run, XV101_Open, H001_AlarmLamp, DB_Station.Pressure_bar, DB_Station.Speed_pct, model:tank.level_pct, model:demand_m3h — CSV, SHA-256 0bf1518fa8f0de07585ac484297d4d57fe5af3412ba70107e9e62e14681bd69d
T11_ControllerOutputLimits — PASS Controller output stays between the minimum speed (30 %) and 100 % · 100 samples every 500 ms of PLC time #3 Setup: pumps stopped, valve closed, Day set active #1 #7 Setup: no alarm left #2 #9 Setup: duty pump P-101 confirms running #3 #10 Setup: header pressure at the setpoint #4 #14 Speed limited to the minimum speed #5 #15 Never below 30 % #6 #18 Speed limited to 100 % #7 #19 Never above 100 % #8 DB_Station.Pressure_bar DB_Station.Speed_pct model:tank.level_pct model:demand_m3h 0 20 40 60 80 100 DB_Station.Pressure_bar DB_Station.Speed_pct model:tank.level_pct model:demand_m3h P1_RunP1_Run P2_RunP2_Run XV101_OpenXV101_Open H001_AlarmLampH001_AlarmLamp 0 5 10 15 20 25 30 35 40 45 PLC time (virtual), s
T11_ControllerOutputLimits: P1_Run, P2_Run, XV101_Open, H001_AlarmLamp, DB_Station.Pressure_bar, DB_Station.Speed_pct, model:tank.level_pct, model:demand_m3h — CSV, SHA-256 2244efc6f9c320543703ac8fd922eb514fd821e0bf9a078691938be393d9161f
T12_ConsumptionStep_PressureDeviation — XFAIL Consumption step 12 -> 30 m3/h: pressure within 0.3 bar of the setpoint · 36 samples every 500 ms of PLC time #3 Setup: pumps stopped, valve closed, Day set active #1 #7 Setup: no alarm left #2 #9 Setup: duty pump P-101 confirms running #3 #10 Setup: header pressure at the setpoint #4 #13 Header pressure within 0.3 bar of the setpoint for 60 s #5 DB_Station.Pressure_bar DB_Station.Speed_pct model:tank.level_pct model:demand_m3h 0 20 40 60 80 100 DB_Station.Pressure_bar DB_Station.Speed_pct model:tank.level_pct model:demand_m3h #13 Header pressure within 0.3 bar of the setpoint for 60 s: DB_Station.Pressure_bar = 3.5366 at 16.5 s P1_RunP1_Run P2_RunP2_Run XV101_OpenXV101_Open H001_AlarmLampH001_AlarmLamp 0 2 4 6 8 10 12 14 16 PLC time (virtual), s
T12_ConsumptionStep_PressureDeviation: P1_Run, P2_Run, XV101_Open, H001_AlarmLamp, DB_Station.Pressure_bar, DB_Station.Speed_pct, model:tank.level_pct, model:demand_m3h — CSV, SHA-256 89722dd9e0ad64220280aa437abb55a60adfd371afc1405d317d42da90d9fa52
T13_PressureTransmitterFault_Fallback — PASS Pressure transmitter wire break: alarm, pumps continue at the fallback speed 70 % · 65 samples every 500 ms of PLC time #3 Setup: pumps stopped, valve closed, Day set active #1 #7 Setup: no alarm left #2 #9 Setup: duty pump P-101 confirms running #3 #10 Setup: header pressure at the setpoint #4 #13 A_PressureSensor, speed 70 % #5 #14 Speed reference 70 % on the drive #6 #15 The pump keeps running #7 #18 Back to pressure control #8 DB_Station.Pressure_bar DB_Station.Speed_pct model:tank.level_pct model:demand_m3h 0 20 40 60 80 100 DB_Station.Pressure_bar DB_Station.Speed_pct model:tank.level_pct model:demand_m3h P1_RunP1_Run P2_RunP2_Run XV101_OpenXV101_Open H001_AlarmLampH001_AlarmLamp 0 5 10 15 20 25 30 PLC time (virtual), s
T13_PressureTransmitterFault_Fallback: P1_Run, P2_Run, XV101_Open, H001_AlarmLamp, DB_Station.Pressure_bar, DB_Station.Speed_pct, model:tank.level_pct, model:demand_m3h — CSV, SHA-256 0d2e6fc644bc6e3a7ac8c9f7f169c7130bc061f509ef63b21fd65f37c916dac8
T14_HighPressureTrip_LatchedUntilAck — PASS High pressure trip stops all pumps and stays active until acknowledged; lamp H-001 · 56 samples every 500 ms of PLC time #3 Setup: pumps stopped, valve closed, Day set active #1 #7 Setup: no alarm left #2 #9 Setup: duty pump P-101 confirms running #3 #10 Setup: header pressure at the setpoint #4 #13 All pumps stop, A_HighPressure, lamp on #5 #15 The alarm stays active #6 #17 Trip stays latched without acknowledge #7 #19 Alarm and lamp off, duty pump restarts #8 #20 One pump running again #9 DB_Station.Pressure_bar DB_Station.Speed_pct model:tank.level_pct model:demand_m3h 0 20 40 60 80 100 DB_Station.Pressure_bar DB_Station.Speed_pct model:tank.level_pct model:demand_m3h P1_RunP1_Run P2_RunP2_Run XV101_OpenXV101_Open H001_AlarmLampH001_AlarmLamp 0 5 10 15 20 25 PLC time (virtual), s
T14_HighPressureTrip_LatchedUntilAck: P1_Run, P2_Run, XV101_Open, H001_AlarmLamp, DB_Station.Pressure_bar, DB_Station.Speed_pct, model:tank.level_pct, model:demand_m3h — CSV, SHA-256 a71bed528e17218827179809556250a85e1a9fc8977cb1e30e7a36de588550bb
T15_LowPressureWarning — PASS Pipe burst: A_LowPressure after 10 s below 2.0 bar, pumps keep running · 56 samples every 500 ms of PLC time #3 Setup: pumps stopped, valve closed, Day set active #1 #7 Setup: no alarm left #2 #9 Setup: duty pump P-101 confirms running #3 #10 Setup: header pressure at the setpoint #4 #13 Pressure falls below 2 bar #5 #14 No warning during the 10 s delay #6 #15 A_LowPressure #7 #16 Warning only: the duty pump keeps running #8 DB_Station.Pressure_bar DB_Station.Speed_pct model:tank.level_pct model:demand_m3h 0 20 40 60 80 100 DB_Station.Pressure_bar DB_Station.Speed_pct model:tank.level_pct model:demand_m3h P1_RunP1_Run P2_RunP2_Run XV101_OpenXV101_Open H001_AlarmLampH001_AlarmLamp 0 5 10 15 20 25 PLC time (virtual), s
T15_LowPressureWarning: P1_Run, P2_Run, XV101_Open, H001_AlarmLamp, DB_Station.Pressure_bar, DB_Station.Speed_pct, model:tank.level_pct, model:demand_m3h — CSV, SHA-256 189972d2cf028341a59a90c671fbd2e995c36da44914280275d89edc4556e43a
T16_DutySelection_LowerRunHours[lower=1] — FAIL Station start: P-101 has the lower run hours and becomes the duty pump · 6 samples every 500 ms of PLC time #3 Setup: pumps stopped, valve closed, Day set active #1 #7 Setup: no alarm left #2 #12 P-101 is the duty pump #3 DB_Station.Pressure_bar DB_Station.Speed_pct model:tank.level_pct model:demand_m3h 0 20 40 60 80 100 DB_Station.Pressure_bar DB_Station.Speed_pct model:tank.level_pct model:demand_m3h P1_RunP1_Run P2_RunP2_Run XV101_OpenXV101_Open H001_AlarmLampH001_AlarmLamp #12 P-101 is the duty pump failed at 2.1 s 0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 PLC time (virtual), s
T16_DutySelection_LowerRunHours[lower=1]: P1_Run, P2_Run, XV101_Open, H001_AlarmLamp, DB_Station.Pressure_bar, DB_Station.Speed_pct, model:tank.level_pct, model:demand_m3h — CSV, SHA-256 235c5fadbb796b893a73dba73f43eb86175a46d3f41e4554ef4fec18b41aec12
T16_DutySelection_LowerRunHours[lower=2] — FAIL Station start: P-102 has the lower run hours and becomes the duty pump · 5 samples every 500 ms of PLC time #3 Setup: pumps stopped, valve closed, Day set active #1 #7 Setup: no alarm left #2 #12 P-102 is the duty pump #3 DB_Station.Pressure_bar DB_Station.Speed_pct model:tank.level_pct model:demand_m3h 0 20 40 60 80 100 DB_Station.Pressure_bar DB_Station.Speed_pct model:tank.level_pct model:demand_m3h P1_RunP1_Run P2_RunP2_Run XV101_OpenXV101_Open H001_AlarmLampH001_AlarmLamp #12 P-102 is the duty pump failed at 2 s 0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 PLC time (virtual), s
T16_DutySelection_LowerRunHours[lower=2]: P1_Run, P2_Run, XV101_Open, H001_AlarmLamp, DB_Station.Pressure_bar, DB_Station.Speed_pct, model:tank.level_pct, model:demand_m3h — CSV, SHA-256 a99de4e1588772c66199c53490e4e2c782c34728b8bccf92394e23427753ed6a
T17_DutyAlternation — PASS Duty pump changes over after the alternation time (60 s in the test) · 125 samples every 500 ms of PLC time #3 Setup: pumps stopped, valve closed, Day set active #1 #7 Setup: no alarm left #2 #11 Equal run hours: P-101 is duty #3 #12 P-101 runs alone until the alternation time #4 #13 Change-over to P-102 #5 #14 Pressure back at the setpoint #6 DB_Station.Pressure_bar DB_Station.Speed_pct model:tank.level_pct model:demand_m3h 0 20 40 60 80 100 DB_Station.Pressure_bar DB_Station.Speed_pct model:tank.level_pct model:demand_m3h P1_RunP1_Run P2_RunP2_Run XV101_OpenXV101_Open H001_AlarmLampH001_AlarmLamp 0 10 20 30 40 50 60 PLC time (virtual), s
T17_DutyAlternation: P1_Run, P2_Run, XV101_Open, H001_AlarmLamp, DB_Station.Pressure_bar, DB_Station.Speed_pct, model:tank.level_pct, model:demand_m3h — CSV, SHA-256 0d4e5201b9cc0ac46fe84146c72a0d45bfb9d30172dfaf4fb1171d2b5c253333
T18_AssistPump — PASS Assist pump starts after 10 s at 100 % speed and stops below 80 % speed · 101 samples every 500 ms of PLC time #3 Setup: pumps stopped, valve closed, Day set active #1 #7 Setup: no alarm left #2 #9 Setup: duty pump P-101 confirms running #3 #10 Setup: header pressure at the setpoint #4 #13 Duty pump at 100 % #5 #14 No assist before the 10 s delay #6 #15 Assist pump P-102 starts #7 #16 Two pumps hold the setpoint #8 #18 Assist pump stops after 10 s below 80 % #9 #19 Duty pump alone at the setpoint #10 DB_Station.Pressure_bar DB_Station.Speed_pct model:tank.level_pct model:demand_m3h 0 20 40 60 80 100 DB_Station.Pressure_bar DB_Station.Speed_pct model:tank.level_pct model:demand_m3h P1_RunP1_Run P2_RunP2_Run XV101_OpenXV101_Open H001_AlarmLampH001_AlarmLamp 0 5 10 15 20 25 30 35 40 45 PLC time (virtual), s
T18_AssistPump: P1_Run, P2_Run, XV101_Open, H001_AlarmLamp, DB_Station.Pressure_bar, DB_Station.Speed_pct, model:tank.level_pct, model:demand_m3h — CSV, SHA-256 cc8df20d8005e2ac8000ee34a26a6264ad011456b251b189eeb7f6e845b741d2
T19_FeedbackLoss_Failover — FAIL Duty pump loses its running feedback: A_P1_NoFeedback after 5 s, P-102 takes over within 2 s · 49 samples every 500 ms of PLC time #3 Setup: pumps stopped, valve closed, Day set active #1 #7 Setup: no alarm left #2 #9 Setup: duty pump P-101 confirms running #3 #10 Setup: header pressure at the setpoint #4 #13 No alarm during the 5 s feedback timeout #5 #14 A_P1_NoFeedback, P-101 unavailable #6 #15 Standby P-102 takes over within 2 s #7 DB_Station.Pressure_bar DB_Station.Speed_pct model:tank.level_pct model:demand_m3h 0 20 40 60 80 100 DB_Station.Pressure_bar DB_Station.Speed_pct model:tank.level_pct model:demand_m3h P1_RunP1_Run P2_RunP2_Run XV101_OpenXV101_Open H001_AlarmLampH001_AlarmLamp #15 Standby P-102 takes over within 2 s failed at 23.1 s 0 2 4 6 8 10 12 14 16 18 20 22 PLC time (virtual), s
T19_FeedbackLoss_Failover: P1_Run, P2_Run, XV101_Open, H001_AlarmLamp, DB_Station.Pressure_bar, DB_Station.Speed_pct, model:tank.level_pct, model:demand_m3h — CSV, SHA-256 787e5c93502d0051cb561424fb1203e8f0c0ddc39a2c7ca9a61b46a18a02689b
T20_VfdFault — PASS VFD fault stops the pump and raises A_P1_VfdFault · 37 samples every 500 ms of PLC time #3 Setup: pumps stopped, valve closed, Day set active #1 #7 Setup: no alarm left #2 #9 Setup: duty pump P-101 confirms running #3 #10 Setup: header pressure at the setpoint #4 #13 P-101 stops, A_P1_VfdFault #5 #16 Alarm cleared #6 DB_Station.Pressure_bar DB_Station.Speed_pct model:tank.level_pct model:demand_m3h 0 20 40 60 80 100 DB_Station.Pressure_bar DB_Station.Speed_pct model:tank.level_pct model:demand_m3h P1_RunP1_Run P2_RunP2_Run XV101_OpenXV101_Open H001_AlarmLampH001_AlarmLamp 0 2 4 6 8 10 12 14 16 PLC time (virtual), s
T20_VfdFault: P1_Run, P2_Run, XV101_Open, H001_AlarmLamp, DB_Station.Pressure_bar, DB_Station.Speed_pct, model:tank.level_pct, model:demand_m3h — CSV, SHA-256 61c5b584bf5d71d08d8ddc76e573a597bb784cd4b94580593f251bf5ef158092
T21_RunHoursAndStarts — PASS Run hours and starts are counted per pump · 734 samples every 500 ms of PLC time #3 Setup: pumps stopped, valve closed, Day set active #1 #7 Setup: no alarm left #2 #11 P-101 runs #3 #13 P-101: 0.1 h, P-102: 0 h #4 #15 #15 #17 Second start counted, run hours keep counting #6 DB_Station.Pressure_bar DB_Station.Speed_pct model:tank.level_pct model:demand_m3h 0 20 40 60 80 100 DB_Station.Pressure_bar DB_Station.Speed_pct model:tank.level_pct model:demand_m3h P1_RunP1_Run P2_RunP2_Run XV101_OpenXV101_Open H001_AlarmLampH001_AlarmLamp 0 1 2 3 4 5 6 PLC time (virtual), min
T21_RunHoursAndStarts: P1_Run, P2_Run, XV101_Open, H001_AlarmLamp, DB_Station.Pressure_bar, DB_Station.Speed_pct, model:tank.level_pct, model:demand_m3h — CSV, SHA-256 33c4df3de710ac6eea2f602c35fe101dc65c89de94d49f60f3035b187388e34f
T22_SetpointSets — PASS Setpoint sets Night and Maintenance are loaded without stopping the pumps · 80 samples every 500 ms of PLC time #3 Setup: pumps stopped, valve closed, Day set active #1 #7 Setup: no alarm left #2 #9 Setup: duty pump P-101 confirms running #3 #10 Setup: header pressure at the setpoint #4 #13 Night set active: 3.0 bar #5 #14 The duty pump keeps running #6 #15 Pressure follows the Night setpoint #7 #17 Maintenance set active: 3.5 bar, alternation 1 h #8 #18 Pressure follows the Maintenance setpoint #9 DB_Station.Pressure_bar DB_Station.Speed_pct model:tank.level_pct model:demand_m3h 0 20 40 60 80 100 DB_Station.Pressure_bar DB_Station.Speed_pct model:tank.level_pct model:demand_m3h P1_RunP1_Run P2_RunP2_Run XV101_OpenXV101_Open H001_AlarmLampH001_AlarmLamp 0 5 10 15 20 25 30 35 PLC time (virtual), s
T22_SetpointSets: P1_Run, P2_Run, XV101_Open, H001_AlarmLamp, DB_Station.Pressure_bar, DB_Station.Speed_pct, model:tank.level_pct, model:demand_m3h — CSV, SHA-256 00822da9c96a0c5259bc50d6e7bddb0d9012f2ed635e4e87f1b542f2f61b8aeb

4. Requirement coverage

RequirementStatusTests
BPS-3.1-R01PASST01_ModeOff_AllOutputsOff PASS, T02_Manual_PumpsIndividually PASS
BPS-3.1-R02PASST01_ModeOff_AllOutputsOff PASS
BPS-3.2-R01PASST02_Manual_PumpsIndividually PASS
BPS-3.2-R02PASST03_Manual_ProtectionsActive PASS
BPS-3.3-R01PASST04_EStop_StopsAll_RestartAfterAck PASS
BPS-3.3-R02PASST04_EStop_StopsAll_RestartAfterAck PASS
BPS-4.1-R01PASST05_Refill_Hysteresis PASS
BPS-4.1-R02PASST05_Refill_Hysteresis PASS
BPS-4.2-R01PASST06_HighLevel_ValveStuckOpen PASS
BPS-4.3-R01PASST06_HighLevel_ValveStuckOpen PASS
BPS-4.4-R01N/AT07_MainsPressureSwitch N/A
BPS-5.1-R01FAILINGT08_DryRun_StopAndRestartHysteresis FAIL
BPS-5.1-R02FAILINGT08_DryRun_StopAndRestartHysteresis FAIL
BPS-5.2-R01PASST09_LevelTransmitterFault PASS
BPS-6.1-R01PASST10_PressureControl_SteadyState PASS
BPS-6.1-R02PASST10_PressureControl_SteadyState PASS
BPS-8.1-R01FAILINGT10_PressureControl_SteadyState PASS, T16_DutySelection_LowerRunHours[lower=1] FAIL, T16_DutySelection_LowerRunHours[lower=2] FAIL
BPS-6.1-R03PASST11_ControllerOutputLimits PASS
BPS-6.2-R01KNOWN DEVIATIONT12_ConsumptionStep_PressureDeviation XFAIL
BPS-6.3-R01PASST13_PressureTransmitterFault_Fallback PASS
BPS-7.1-R01PASST14_HighPressureTrip_LatchedUntilAck PASS
BPS-7.1-R02PASST14_HighPressureTrip_LatchedUntilAck PASS
BPS-10-R01PASST14_HighPressureTrip_LatchedUntilAck PASS
BPS-10-R02PASST14_HighPressureTrip_LatchedUntilAck PASS
BPS-7.2-R01PASST15_LowPressureWarning PASS
BPS-8.1-R02FAILINGT16_DutySelection_LowerRunHours[lower=1] FAIL, T16_DutySelection_LowerRunHours[lower=2] FAIL
BPS-8.1-R03PASST17_DutyAlternation PASS
BPS-8.2-R01PASST18_AssistPump PASS
BPS-8.2-R02PASST18_AssistPump PASS
BPS-8.3-R01FAILINGT19_FeedbackLoss_Failover FAIL
BPS-8.3-R02FAILINGT19_FeedbackLoss_Failover FAIL
BPS-8.3-R03PASST20_VfdFault PASS
BPS-8.4-R01PASST21_RunHoursAndStarts PASS
BPS-9-R01PASST22_SetpointSets PASS
BPS-9-R02PASST22_SetpointSets PASS

5. Traceability

Requirements file requirements.json (SHA-256 d529cca3067947f243dfc1c2c6a89fcd4cd89940e7905617823c452b461cd525), specification ../spec/Pump_Station_Spec.md.

35requirements
100.0 %covered (35 direct, 0 by section)
0without tests
0tests without requirements
6FAILING
1KNOWN DEVIATION
1N/A
27PASS

Coverage gaps

Requirements without tests (0)none
Requirements whose tests fail (6)BPS-5.1-R01, BPS-5.1-R02, BPS-8.1-R01, BPS-8.1-R02, BPS-8.3-R01, BPS-8.3-R02
Requirements whose tests are all N/A (1)BPS-4.4-R01
Requirements with known deviations (XFAIL) (1)BPS-6.2-R01
Tests without requirements (0)none

Matrix

RequirementCategory / priorityStatusTests (last result)PLC objects
BPS-3.1-R01
The station shall have the operating modes Off, Manual and Auto, selected by the operator on the HMI.
function
high
PASST01_ModeOff_AllOutputsOff PASS, T02_Manual_PumpsIndividually PASSDB_Operator, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Station.Alarms.Common, DB_Station.Pressure_bar, DB_Station.Pump[1].RunHours, DB_Station.Pump[2].RunHours, H001_AlarmLamp, P1_Run, P1_RunFB, P1_SpeedRef, P2_Run … (17 tags)
BPS-3.1-R02
In mode Off all pump and valve outputs shall be switched off.
function
high
PASST01_ModeOff_AllOutputsOff PASSDB_Operator, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Station.Alarms.Common, DB_Station.Pressure_bar, DB_Station.Pump[1].RunHours, DB_Station.Pump[2].RunHours, H001_AlarmLamp, P1_Run, P1_RunFB, P1_SpeedRef, P2_Run … (17 tags)
BPS-3.2-R01
In mode Manual the operator shall start and stop each pump individually, and a started pump shall run at the manual speed setpoint.
function
high
PASST02_Manual_PumpsIndividually PASSDB_Operator, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Station.Alarms.Common, DB_Station.Pump[1].RunHours, DB_Station.Pump[2].RunHours, H001_AlarmLamp, P1_Run, P2_Run, P2_SpeedRef
BPS-3.2-R02
The dry-run protection, the high pressure trip and the emergency stop shall stay active in mode Manual.
safety
high
PASST03_Manual_ProtectionsActive PASSDB_Operator, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Station.Alarms.Common, DB_Station.Alarms.EStop, DB_Station.Alarms.HighPressure, DB_Station.Pump[1].RunHours, DB_Station.Pump[2].RunHours, H001_AlarmLamp, P1_Run
BPS-3.3-R01
When the emergency stop circuit opens, all pumps shall stop and the inlet valve shall close within 0.5 s.
safety
high
PASST04_EStop_StopsAll_RestartAfterAck PASSDB_Operator, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Station.Alarms.Common, DB_Station.Alarms.EStop, DB_Station.Pressure_bar, DB_Station.PumpsRunning, DB_Station.Pump[1].RunHours, DB_Station.Pump[2].RunHours, DB_Station.StationRun, H001_AlarmLamp, P1_Run … (18 tags)
BPS-3.3-R02
After the emergency stop circuit has been closed again, the pumps shall restart only after the operator has acknowledged the alarm.
safety
high
PASST04_EStop_StopsAll_RestartAfterAck PASSDB_Operator, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Station.Alarms.Common, DB_Station.Alarms.EStop, DB_Station.Pressure_bar, DB_Station.PumpsRunning, DB_Station.Pump[1].RunHours, DB_Station.Pump[2].RunHours, DB_Station.StationRun, H001_AlarmLamp, P1_Run … (18 tags)
BPS-4.1-R01
In modes Manual and Auto the inlet valve XV-101 shall open when the tank level falls below the refill start level (default 40 %).
setpoint
high
PASST05_Refill_Hysteresis PASSDB_Operator, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Station.Alarms.Common, DB_Station.Pressure_bar, DB_Station.Pump[1].RunHours, DB_Station.Pump[2].RunHours, H001_AlarmLamp, P1_RunFB, XV101_Open, XV101_ZSC, XV101_ZSO
BPS-4.1-R02
The inlet valve shall close when the tank level rises above the refill stop level (default 85 %).
setpoint
high
PASST05_Refill_Hysteresis PASSDB_Operator, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Station.Alarms.Common, DB_Station.Pressure_bar, DB_Station.Pump[1].RunHours, DB_Station.Pump[2].RunHours, H001_AlarmLamp, P1_RunFB, XV101_Open, XV101_ZSC, XV101_ZSO
BPS-4.2-R01
If the tank level exceeds the high level limit (default 95 %), the alarm A_HighLevel shall be raised and the inlet valve shall be closed.
alarm
high
PASST06_HighLevel_ValveStuckOpen PASSDB_Operator, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Station.Alarms.Common, DB_Station.Alarms.ValveFault, DB_Station.Pressure_bar, DB_Station.Pump[1].RunHours, DB_Station.Pump[2].RunHours, H001_AlarmLamp, P1_RunFB, XV101_Open, XV101_ZSC
BPS-4.3-R01
If the inlet valve does not reach the commanded end position within 15 s, the alarm A_ValveFault shall be raised.
alarm
high
PASST06_HighLevel_ValveStuckOpen PASSDB_Operator, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Station.Alarms.Common, DB_Station.Alarms.ValveFault, DB_Station.Pressure_bar, DB_Station.Pump[1].RunHours, DB_Station.Pump[2].RunHours, H001_AlarmLamp, P1_RunFB, XV101_Open, XV101_ZSC
BPS-4.4-R01
If the station is equipped with the optional mains pressure switch PS-100, a missing mains pressure shall raise the warning A_MainsLow.
alarm
high
N/AT07_MainsPressureSwitch N/ADB_Station — DB_Station.Alarms.MainsLow
BPS-5.1-R01
If the tank level falls below the low-low level (default 10 %), all pumps shall stop within 1 s and the alarm A_LowLevel shall be raised.
alarm
high
FAILINGT08_DryRun_StopAndRestartHysteresis FAILDB_Operator, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Station.Alarms.Common, DB_Station.Alarms.LowLevel, DB_Station.Pressure_bar, DB_Station.PumpsRunning, DB_Station.Pump[1].RunHours, DB_Station.Pump[2].RunHours, H001_AlarmLamp, P1_RunFB
BPS-5.1-R02
The pumps shall not restart before the tank level has risen above the low-low level plus the restart hysteresis (default 10 %).
setpoint
high
FAILINGT08_DryRun_StopAndRestartHysteresis FAILDB_Operator, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Station.Alarms.Common, DB_Station.Alarms.LowLevel, DB_Station.Pressure_bar, DB_Station.PumpsRunning, DB_Station.Pump[1].RunHours, DB_Station.Pump[2].RunHours, H001_AlarmLamp, P1_RunFB
BPS-5.2-R01
If the level signal is out of range (wire break or short circuit), the alarm A_LevelSensor shall be raised, all pumps shall stop and the inlet valve shall close.
alarm
high
PASST09_LevelTransmitterFault PASSDB_Operator, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Station.Alarms.Common, DB_Station.Alarms.LevelSensor, DB_Station.Pressure_bar, DB_Station.PumpsRunning, DB_Station.Pump[1].RunHours, DB_Station.Pump[2].RunHours, DB_Station.StationRun, H001_AlarmLamp, P1_Run … (18 tags)
BPS-6.1-R01
In mode Auto the speed of the running pumps shall be controlled by a PI controller so that the header pressure follows the pressure setpoint (default 4.0 bar).
setpoint
high
PASST10_PressureControl_SteadyState PASSDB_Operator, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Station.Alarms.Common, DB_Station.AssistActive, DB_Station.DutyPump, DB_Station.Pressure_bar, DB_Station.PumpsRunning, DB_Station.Pump[1].RunHours, DB_Station.Pump[2].RunHours, H001_AlarmLamp, P1_Run … (17 tags)
BPS-6.1-R02
At constant consumption the header pressure shall stay within 0.2 bar of the setpoint.
setpoint
high
PASST10_PressureControl_SteadyState PASSDB_Operator, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Station.Alarms.Common, DB_Station.AssistActive, DB_Station.DutyPump, DB_Station.Pressure_bar, DB_Station.PumpsRunning, DB_Station.Pump[1].RunHours, DB_Station.Pump[2].RunHours, H001_AlarmLamp, P1_Run … (17 tags)
BPS-6.1-R03
The controller output shall be limited to the range from the minimum speed (default 30 %) to 100 %.
setpoint
high
PASST11_ControllerOutputLimits PASSDB_Operator, DB_Settings, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Settings.Active.Pressure_SP, DB_Station.Alarms.Common, DB_Station.Pressure_bar, DB_Station.Pump[1].RunHours, DB_Station.Pump[2].RunHours, DB_Station.Speed_pct, H001_AlarmLamp, P1_RunFB
BPS-6.2-R01
After a step of the consumption from 12 to 30 m3/h the header pressure shall not deviate more than 0.3 bar from the setpoint.
setpoint
high
KNOWN DEVIATIONT12_ConsumptionStep_PressureDeviation XFAILDB_Operator, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Station.Alarms.Common, DB_Station.Pressure_bar, DB_Station.Pump[1].RunHours, DB_Station.Pump[2].RunHours, H001_AlarmLamp, P1_RunFB
BPS-6.3-R01
If the pressure signal is out of range, the alarm A_PressureSensor shall be raised and the running pumps shall continue at the fallback speed (default 70 %).
alarm
high
PASST13_PressureTransmitterFault_Fallback PASSDB_Operator, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Station.Alarms.Common, DB_Station.Alarms.PressureSensor, DB_Station.Pressure_bar, DB_Station.Pump[1].RunHours, DB_Station.Pump[2].RunHours, DB_Station.Speed_pct, H001_AlarmLamp, P1_RunFB, P1_SpeedRef
BPS-7.1-R01
If the header pressure exceeds the high pressure trip limit (default 6.0 bar), all pumps shall stop and the alarm A_HighPressure shall be raised.
alarm
high
PASST14_HighPressureTrip_LatchedUntilAck PASSDB_Operator, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Station.Alarms.Common, DB_Station.Alarms.HighPressure, DB_Station.Pressure_bar, DB_Station.PumpsRunning, DB_Station.Pump[1].RunHours, DB_Station.Pump[2].RunHours, DB_Station.StationRun, H001_AlarmLamp, P1_Run … (17 tags)
BPS-7.1-R02
A high pressure trip shall remain active until the operator acknowledges it on the HMI.
function
high
PASST14_HighPressureTrip_LatchedUntilAck PASSDB_Operator, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Station.Alarms.Common, DB_Station.Alarms.HighPressure, DB_Station.Pressure_bar, DB_Station.PumpsRunning, DB_Station.Pump[1].RunHours, DB_Station.Pump[2].RunHours, DB_Station.StationRun, H001_AlarmLamp, P1_Run … (17 tags)
BPS-7.2-R01
If the header pressure stays below the low pressure limit (default 2.0 bar) for longer than 10 s while a pump runs, the warning A_LowPressure shall be raised.
alarm
high
PASST15_LowPressureWarning PASSDB_Operator, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Station.Alarms.Common, DB_Station.Alarms.LowPressure, DB_Station.Pressure_bar, DB_Station.Pump[1].RunHours, DB_Station.Pump[2].RunHours, H001_AlarmLamp, P1_Run, P1_RunFB
BPS-8.1-R01
In mode Auto one pump shall run as duty pump while the other pump is the standby pump.
function
high
FAILINGT10_PressureControl_SteadyState PASS, T16_DutySelection_LowerRunHours[lower=1] FAIL, T16_DutySelection_LowerRunHours[lower=2] FAILDB_Operator, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Station.Alarms.Common, DB_Station.AssistActive, DB_Station.DutyPump, DB_Station.Pressure_bar, DB_Station.PumpsRunning, DB_Station.Pump[1].RunHours, DB_Station.Pump[2].RunHours, H001_AlarmLamp, P1_Run … (18 tags)
BPS-8.1-R02
At every start of the station the available pump with the lower run hours shall become the duty pump.
function
high
FAILINGT16_DutySelection_LowerRunHours[lower=1] FAIL, T16_DutySelection_LowerRunHours[lower=2] FAILDB_Operator, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Station.Alarms.Common, DB_Station.DutyPump, DB_Station.PumpsRunning, DB_Station.Pump[1].RunHours, DB_Station.Pump[2].RunHours, H001_AlarmLamp, P1_Run, P1_RunFB, P2_Run … (16 tags)
BPS-8.1-R03
The duty pump shall change over to the standby pump after the alternation time (default 24 h) of continuous running.
setpoint
high
PASST17_DutyAlternation PASSDB_Operator, DB_Settings, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Settings.Active.Alternation_Time, DB_Station.Alarms.Common, DB_Station.DutyPump, DB_Station.Pressure_bar, DB_Station.Pump[1].RunHours, DB_Station.Pump[2].RunHours, H001_AlarmLamp, P1_Run, P2_Run
BPS-8.2-R01
If the duty pump runs at 100 % speed for longer than the assist delay (default 10 s) and the header pressure is more than 0.3 bar below the setpoint, the standby pump shall be started as assist pump.
function
high
PASST18_AssistPump PASSDB_Operator, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Station.Alarms.Common, DB_Station.AssistActive, DB_Station.Pressure_bar, DB_Station.Pump[1].RunHours, DB_Station.Pump[2].RunHours, DB_Station.Speed_pct, H001_AlarmLamp, P1_Run, P1_RunFB … (16 tags)
BPS-8.2-R02
The assist pump shall be stopped when the common speed stays below the assist stop speed (default 80 %) for 10 s.
setpoint
high
PASST18_AssistPump PASSDB_Operator, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Station.Alarms.Common, DB_Station.AssistActive, DB_Station.Pressure_bar, DB_Station.Pump[1].RunHours, DB_Station.Pump[2].RunHours, DB_Station.Speed_pct, H001_AlarmLamp, P1_Run, P1_RunFB … (16 tags)
BPS-8.3-R01
If a pump does not confirm running within the feedback timeout (default 5 s) after its start command, the alarm A_Pn_NoFeedback shall be raised and the pump shall be marked as unavailable.
alarm
high
FAILINGT19_FeedbackLoss_Failover FAILDB_Operator, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Station.Alarms.Common, DB_Station.DutyPump, DB_Station.Pressure_bar, DB_Station.Pump[1].Alm_NoFeedback, DB_Station.Pump[1].Available, DB_Station.Pump[1].RunHours, DB_Station.Pump[2].RunHours, H001_AlarmLamp, P1_Run … (18 tags)
BPS-8.3-R02
If the duty pump fails, the standby pump shall take over within 2 s after the failure has been detected.
alarm
high
FAILINGT19_FeedbackLoss_Failover FAILDB_Operator, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Station.Alarms.Common, DB_Station.DutyPump, DB_Station.Pressure_bar, DB_Station.Pump[1].Alm_NoFeedback, DB_Station.Pump[1].Available, DB_Station.Pump[1].RunHours, DB_Station.Pump[2].RunHours, H001_AlarmLamp, P1_Run … (18 tags)
BPS-8.3-R03
A VFD fault signal shall stop the pump and raise the alarm A_Pn_VfdFault.
alarm
high
PASST20_VfdFault PASSDB_Operator, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Station.Alarms.Common, DB_Station.Pressure_bar, DB_Station.Pump[1].Alm_VfdFault, DB_Station.Pump[1].RunHours, DB_Station.Pump[2].RunHours, H001_AlarmLamp, P1_Run, P1_RunFB
BPS-8.4-R01
The PLC shall count the run hours and the number of starts of each pump.
function
high
PASST21_RunHoursAndStarts PASSDB_Operator, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Station.Alarms.Common, DB_Station.Pump[1].RunHours, DB_Station.Pump[1].Starts, DB_Station.Pump[2].RunHours, DB_Station.Pump[2].Starts, H001_AlarmLamp, P1_RunFB
BPS-9-R01
The station shall provide the three setpoint sets Day, Night and Maintenance, which the operator loads as active setpoints on the HMI.
function
high
PASST22_SetpointSets PASSDB_Operator, DB_Settings, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Settings.Active.Alternation_Time, DB_Settings.Active.Pressure_SP, DB_Settings.ActiveSet, DB_Station.Alarms.Common, DB_Station.Pressure_bar, DB_Station.Pump[1].RunHours, DB_Station.Pump[2].RunHours, H001_AlarmLamp, P1_Run … (16 tags)
BPS-9-R02
Loading a setpoint set shall not stop running pumps.
function
high
PASST22_SetpointSets PASSDB_Operator, DB_Settings, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Settings.Active.Alternation_Time, DB_Settings.Active.Pressure_SP, DB_Settings.ActiveSet, DB_Station.Alarms.Common, DB_Station.Pressure_bar, DB_Station.Pump[1].RunHours, DB_Station.Pump[2].RunHours, H001_AlarmLamp, P1_Run … (16 tags)
BPS-10-R01
Every alarm shall switch on the common alarm lamp H-001 until it is acknowledged.
alarm
high
PASST14_HighPressureTrip_LatchedUntilAck PASSDB_Operator, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Station.Alarms.Common, DB_Station.Alarms.HighPressure, DB_Station.Pressure_bar, DB_Station.PumpsRunning, DB_Station.Pump[1].RunHours, DB_Station.Pump[2].RunHours, DB_Station.StationRun, H001_AlarmLamp, P1_Run … (17 tags)
BPS-10-R02
All alarms shall be acknowledged with one acknowledge command on the HMI, and an alarm whose cause is still present shall stay active.
alarm
high
PASST14_HighPressureTrip_LatchedUntilAck PASSDB_Operator, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Station.Alarms.Common, DB_Station.Alarms.HighPressure, DB_Station.Pressure_bar, DB_Station.PumpsRunning, DB_Station.Pump[1].RunHours, DB_Station.Pump[2].RunHours, DB_Station.StationRun, H001_AlarmLamp, P1_Run … (17 tags)

(§) = linked through a section reference (e.g. PREFIX-6.4) rather than the requirement id. PLC objects: data blocks of the tags, blocks named in the test source, then the tags written/checked by the tests.

6. Sign-off

RoleNameDateSignature
Supplier 
Customer