EXPECTED OUTCOME (offline simulation, no PLCSIM) - BPS-1 program v1.1
Generated 2026-11-22 18:16:28 UTC by TAIPilot
PASSED WITH KNOWN DEVIATIONS
1. Identification
| Project | TAIPilotDemo_BPS1 |
|---|---|
| PLC / CPU | PLC_BPS1 / CPU 1511-1 PN |
| DB_Info.Program | BPS-1 |
| DB_Info.ProgVersion | v1.1 |
| PLCSIM instance | offline: Bps1Sim (C# port of demo/plc, v1.1) |
| Suite | BPS-1 booster pump station - FAT on PLCSIM with plant model (bps1_suite.json) |
| Suite SHA-256 | 715e4d1109ce1d455b31ff39ad3ee6bc1bcadb4bbd721b574d91d2f542805138 |
| Run | offline-v1.1 (completed) |
| Run date (UTC) | 2026-11-22 00:00:00 - 2026-11-22 00:00:00 |
| Execution | cycle, 100 ms virtual time per cycle; 0 s wall clock in 1 call(s) |
| Selection | all tests |
| TAIPilot version | offline simulation (Bps1Sim, no PLCSIM) |
2. Summary
23tests
21Passed
0Failed
1Expected fail (known deviation)
1Not applicable
Requirements: 35, without tests: 0, failing: 0.
Notes: Offline simulation: the PLC is the C# test double Bps1Sim, not S7-PLCSIM Advanced.
3. Tests
| # | Test | Requirements | Result | Duration (PLC time) | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | T01_ModeOff_AllOutputsOff Mode Off switches every pump and valve output off Note: plant model: 264 steps, tag I/O 8 ms in 1320 read + 363 write calls, model 19 ms; model events: 0 s set tank.initial_level_m = 3.6; 0 s set tank.initial_level_m = 1.4 | BPS-3.1-R01, BPS-3.1-R02 | PASS 15 steps, 0 failed | 26.1 s wall 0 ms | ||||||||
| 2 | T02_Manual_PumpsIndividually Mode Manual: each pump is started and stopped by the operator and runs at the manual speed Note: plant model: 47 steps, tag I/O 0 ms in 235 read + 30 write calls, model 1 ms; model events: 0 s set tank.initial_level_m = 3.6; 0 s set tank.initial_level_m = 2 | BPS-3.1-R01, BPS-3.2-R01 | PASS 18 steps, 0 failed | 4.4 s wall 0 ms | ||||||||
| 3 | T03_Manual_ProtectionsActive Mode Manual: high pressure trip and emergency stop still stop the pump Note: plant model: 72 steps, tag I/O 0 ms in 360 read + 85 write calls, model 3 ms; model events: 0 s set tank.initial_level_m = 3.6; 0.1 s set tank.initial_level_m = 2; 6.2 s fault PT201: offset 7 (engineering units); 6.3 s fault PT201: cleared; 6.4 s fault forced ESTOP_OK = 0; 6.5 s fault released ESTOP_OK | BPS-3.2-R02 | PASS 18 steps, 0 failed | 6.5 s wall 0 ms | ||||||||
| 4 | T04_EStop_StopsAll_RestartAfterAck Emergency stop: pumps stop and the inlet valve closes at once; restart only after acknowledge Note: plant model: 234 steps, tag I/O 1 ms in 1170 read + 375 write calls, model 14 ms; model events: 0 s set tank.initial_level_m = 3.6; 0 s set tank.initial_level_m = 1.4; 16.1 s fault forced ESTOP_OK = 0; 16.2 s fault released ESTOP_OK | BPS-3.3-R01, BPS-3.3-R02 | PASS 19 steps, 0 failed | 22.9 s wall 0 ms | ||||||||
| 5 | T05_Refill_Hysteresis Inlet valve opens below 40 %, stays open in between, closes above 85 % Note: plant model: 689 steps, tag I/O 2 ms in 3445 read + 870 write calls, model 25 ms; model events: 0 s set tank.initial_level_m = 3.6; 0.1 s set tank.initial_level_m = 2; 19.1 s set tank.initial_level_m = 1.5; 24.2 s set tank.initial_level_m = 3; 27.2 s set tank.initial_level_m = 3.36 | BPS-4.1-R01, BPS-4.1-R02 | PASS 20 steps, 0 failed | 1 min 08 s wall 0 ms | ||||||||
| 6 | T06_HighLevel_ValveStuckOpen Inlet valve stuck open: valve alarm, then high level alarm with the valve commanded closed Note: plant model: 1281 steps, tag I/O 4 ms in 6405 read + 1539 write calls, model 47 ms; model events: 0 s set tank.initial_level_m = 3.6; 0 s set tank.initial_level_m = 3.7; 16 s fault XV101: stuck at 100 %; 127.6 s fault XV101: cleared | BPS-4.2-R01, BPS-4.3-R01 | PASS 18 steps, 0 failed | 2 min 08 s wall 0 ms | ||||||||
| 7 | T07_MainsPressureSwitch Optional mains pressure switch PS-100 raises A_MainsLow Not applicable: BPS-1 is built without the optional mains pressure switch PS-100 (A_MainsLow is held FALSE). | BPS-4.4-R01 | N/A | |||||||||
| 8 | T08_DryRun_StopAndRestartHysteresis Dry-run protection: pumps stop below 10 % and restart only above 20 % Note: plant model: 2175 steps, tag I/O 8 ms in 10875 read + 2552 write calls, model 52 ms; model events: 0 s set tank.initial_level_m = 3.6; 0 s set tank.initial_level_m = 0.48; 16.1 s set inlet_flow.factor = 0; 70.9 s set inlet_flow.factor = 0.2 | BPS-5.1-R01, BPS-5.1-R02 | PASS 20 steps, 0 failed | 3 min 37 s wall 0 ms | ||||||||
| 9 | T09_LevelTransmitterFault Level transmitter wire break: alarm, pumps stop, inlet valve closes Note: plant model: 168 steps, tag I/O 1 ms in 840 read + 239 write calls, model 6 ms; model events: 0 s set tank.initial_level_m = 3.6; 0.1 s set tank.initial_level_m = 1.4; 16.1 s fault LT101: open_circuit; 16.2 s fault LT101: cleared | BPS-5.2-R01 | PASS 18 steps, 0 failed | 16.3 s wall 0 ms | ||||||||
| 10 | T10_PressureControl_SteadyState PI pressure control: 4.0 bar +/- 0.2 bar at constant consumption, one duty pump Note: plant model: 964 steps, tag I/O 3 ms in 4820 read + 1377 write calls, model 36 ms; model events: 0 s set tank.initial_level_m = 3.6; 0.1 s set tank.initial_level_m = 2 | BPS-6.1-R01, BPS-6.1-R02, BPS-8.1-R01 | PASS 14 steps, 0 failed | 1 min 36 s wall 0 ms | ||||||||
| 11 | T11_ControllerOutputLimits Controller output stays between the minimum speed (30 %) and 100 % Note: plant model: 491 steps, tag I/O 1 ms in 2455 read + 614 write calls, model 13 ms; model events: 0 s set tank.initial_level_m = 3.6; 0 s set tank.initial_level_m = 2; 16 s set demand.value = 0; 39.9 s set demand.value = 30 | BPS-6.1-R03 | PASS 19 steps, 0 failed | 48.6 s wall 0 ms | ||||||||
| 12 | T12_ConsumptionStep_PressureDeviation Consumption step 12 -> 30 m3/h: pressure within 0.3 bar of the setpoint Expected to fail: Known deviation: one pump delivers ~20 m3/h at 4 bar and the assist pump may start only after the 10 s assist delay of 8.2, so the pressure dips to ~2.6 bar for about 10 s. Accepted for BPS-1; spec 6.2 to be revised. Note: plant model: 169 steps, tag I/O 1 ms in 845 read + 282 write calls, model 7 ms; model events: 0 s set tank.initial_level_m = 3.6; 0 s set tank.initial_level_m = 2; 16.1 s set demand.value = 30
| BPS-6.2-R01 | XFAIL 13 steps, 1 failed | 16.5 s wall 0 ms | ||||||||
| 13 | T13_PressureTransmitterFault_Fallback Pressure transmitter wire break: alarm, pumps continue at the fallback speed 70 % Note: plant model: 316 steps, tag I/O 1 ms in 1580 read + 459 write calls, model 13 ms; model events: 0 s set tank.initial_level_m = 3.6; 0 s set tank.initial_level_m = 2; 16 s fault PT201: open_circuit; 26.1 s fault PT201: cleared | BPS-6.3-R01 | PASS 18 steps, 0 failed | 31.1 s wall 0 ms | ||||||||
| 14 | T14_HighPressureTrip_LatchedUntilAck High pressure trip stops all pumps and stays active until acknowledged; lamp H-001 Note: plant model: 263 steps, tag I/O 1 ms in 1315 read + 371 write calls, model 9 ms; model events: 0 s set tank.initial_level_m = 3.6; 0 s set tank.initial_level_m = 2; 16 s fault PT201: offset 7 (engineering units); 19.1 s fault PT201: cleared | BPS-7.1-R01, BPS-7.1-R02, BPS-10-R01, BPS-10-R02 | PASS 20 steps, 0 failed | 25.8 s wall 0 ms | ||||||||
| 15 | T15_LowPressureWarning Pipe burst: A_LowPressure after 10 s below 2.0 bar, pumps keep running Note: plant model: 275 steps, tag I/O 1 ms in 1375 read + 464 write calls, model 10 ms; model events: 0 s set tank.initial_level_m = 3.6; 0 s set tank.initial_level_m = 2; 16 s fault hdr: burst 80 m3/h; 27 s fault hdr: cleared | BPS-7.2-R01 | PASS 17 steps, 0 failed | 27.0 s wall 0 ms | ||||||||
| 16 | T16_DutySelection_LowerRunHours[lower=1] Station start: P-101 has the lower run hours and becomes the duty pump Note: plant model: 31 steps, tag I/O 0 ms in 155 read + 12 write calls, model 1 ms; model events: 0 s set tank.initial_level_m = 3.6; 0 s set tank.initial_level_m = 2 | BPS-8.1-R01, BPS-8.1-R02 | PASS 13 steps, 0 failed | 2.8 s wall 0 ms | ||||||||
| 17 | T16_DutySelection_LowerRunHours[lower=2] Station start: P-102 has the lower run hours and becomes the duty pump Note: plant model: 30 steps, tag I/O 0 ms in 150 read + 12 write calls, model 0 ms; model events: 0 s set tank.initial_level_m = 3.6; 0 s set tank.initial_level_m = 2 | BPS-8.1-R01, BPS-8.1-R02 | PASS 13 steps, 0 failed | 2.7 s wall 0 ms | ||||||||
| 18 | T17_DutyAlternation Duty pump changes over after the alternation time (60 s in the test) Note: plant model: 615 steps, tag I/O 2 ms in 3075 read + 911 write calls, model 22 ms; model events: 0 s set tank.initial_level_m = 3.6; 0 s set tank.initial_level_m = 2 | BPS-8.1-R03 | PASS 14 steps, 0 failed | 1 min 01 s wall 0 ms | ||||||||
| 19 | T18_AssistPump Assist pump starts after 10 s at 100 % speed and stops below 80 % speed Note: plant model: 488 steps, tag I/O 2 ms in 2440 read + 846 write calls, model 19 ms; model events: 0 s set tank.initial_level_m = 3.6; 0 s set tank.initial_level_m = 2; 16 s set demand.value = 30; 31.6 s set demand.value = 12 | BPS-8.2-R01, BPS-8.2-R02 | PASS 19 steps, 0 failed | 48.3 s wall 0 ms | ||||||||
| 20 | T19_FeedbackLoss_Failover Duty pump loses its running feedback: A_P1_NoFeedback after 5 s, P-102 takes over within 2 s Note: plant model: 266 steps, tag I/O 1 ms in 1330 read + 409 write calls, model 7 ms; model events: 0 s set tank.initial_level_m = 3.6; 0 s set tank.initial_level_m = 2; 16 s fault P1_fb: never_confirms; 26 s fault P1_fb: cleared | BPS-8.3-R01, BPS-8.3-R02 | PASS 20 steps, 0 failed | 26.1 s wall 0 ms | ||||||||
| 21 | T20_VfdFault VFD fault stops the pump and raises A_P1_VfdFault Note: plant model: 168 steps, tag I/O 0 ms in 840 read + 282 write calls, model 4 ms; model events: 0 s set tank.initial_level_m = 3.6; 0 s set tank.initial_level_m = 2; 16 s fault forced P1_VfdFault = 1; 16.2 s fault released P1_VfdFault | BPS-8.3-R03 | PASS 16 steps, 0 failed | 16.3 s wall 0 ms | ||||||||
| 22 | T21_RunHoursAndStarts Run hours and starts are counted per pump Note: plant model: 3656 steps, tag I/O 11 ms in 18280 read + 4693 write calls, model 112 ms; model events: 0 s set tank.initial_level_m = 3.6; 0 s set tank.initial_level_m = 2 | BPS-8.4-R01 | PASS 18 steps, 0 failed | 6 min 05 s wall 0 ms | ||||||||
| 23 | T22_SetpointSets Setpoint sets Night and Maintenance are loaded without stopping the pumps Note: plant model: 379 steps, tag I/O 1 ms in 1895 read + 684 write calls, model 11 ms; model events: 0 s set tank.initial_level_m = 3.6; 0.1 s set tank.initial_level_m = 2 | BPS-9-R01, BPS-9-R02 | PASS 18 steps, 0 failed | 37.6 s wall 0 ms |
3.1 Trajectories
Recorded PLC tags and plant-model signals over PLC (virtual) time. Shaded: assertion windows (green passed, red failed); dashed: expect_range bounds; red ring / line: first violation. Data: one CSV per test next to this report.
56576cfe21f25deabcaaa993112f6f187249318c8250ecd818fd21ff94cde309588385043f4e4a1b5b1ddd2ce8d4b7ceb9caa570c74090e36f4a84b282bd2859c334bd9eff2305d3626ef546692893d50f76fbe2bba82f79642a6dac2cecff768c09631df22a2022dd1c09ffadab188b57038017071f1bf27148798b7b0e5d30a05fd644f96d34437226da92882baa52c4ee4a04d2fa593df526d8b1af0e8eab7d097571316caab8c7b6c001b4452384a7078866356c9eba45446c074267a97ce40840866cd057c67e04a49396a1abfbd0818d81e5b17f25e95c0ddf0beeaabbb6f49f8bfbfd5ec278828e0ae886210e13031ace304a73b89fea048324a465310abade63677ffab7cec41c74385758611e1d6955f2a4151f2f22cacb3bc936ff2244efc6f9c320543703ac8fd922eb514fd821e0bf9a078691938be393d9161f89722dd9e0ad64220280aa437abb55a60adfd371afc1405d317d42da90d9fa520d2e6fc644bc6e3a7ac8c9f7f169c7130bc061f509ef63b21fd65f37c916dac8871565a8ef51c8946183674cd30a414b3143935e005789afa483c103fb5abdfbf1731d57bcd221dc70b2ce53cc9d536341cc661261e77fb1d4c99f8a6d9bbb5ca174ee6fc744e8d57a1d48c3a19b7f189d05bcd8c17b70f201af028287aaabaa1be402930765fca9457e05574065b1fe33453dfac76aaa766211c6d11f77d08337c937750266286925dab917e3b835749b22117261f54d1be578b9663e0c665acc8df20d8005e2ac8000ee34a26a6264ad011456b251b189eeb7f6e845b741d2bf24acd62cc97cdbb92d6170733df95d3e32c73935730182ba0d45f5fa480ba66b7ece1db88559e6fbdbf5e9c64373ba0588a37747dbee2328d0d8c1cee9eb4cb15c8e4a89d1e367d58622eecfc83130c044167bb5fc4a13dc15f69e8f76e61600822da9c96a0c5259bc50d6e7bddb0d9012f2ed635e4e87f1b542f2f61b8aeb4. Requirement coverage
| Requirement | Status | Tests |
|---|---|---|
| BPS-3.1-R01 | PASS | T01_ModeOff_AllOutputsOff PASS, T02_Manual_PumpsIndividually PASS |
| BPS-3.1-R02 | PASS | T01_ModeOff_AllOutputsOff PASS |
| BPS-3.2-R01 | PASS | T02_Manual_PumpsIndividually PASS |
| BPS-3.2-R02 | PASS | T03_Manual_ProtectionsActive PASS |
| BPS-3.3-R01 | PASS | T04_EStop_StopsAll_RestartAfterAck PASS |
| BPS-3.3-R02 | PASS | T04_EStop_StopsAll_RestartAfterAck PASS |
| BPS-4.1-R01 | PASS | T05_Refill_Hysteresis PASS |
| BPS-4.1-R02 | PASS | T05_Refill_Hysteresis PASS |
| BPS-4.2-R01 | PASS | T06_HighLevel_ValveStuckOpen PASS |
| BPS-4.3-R01 | PASS | T06_HighLevel_ValveStuckOpen PASS |
| BPS-4.4-R01 | N/A | T07_MainsPressureSwitch N/A |
| BPS-5.1-R01 | PASS | T08_DryRun_StopAndRestartHysteresis PASS |
| BPS-5.1-R02 | PASS | T08_DryRun_StopAndRestartHysteresis PASS |
| BPS-5.2-R01 | PASS | T09_LevelTransmitterFault PASS |
| BPS-6.1-R01 | PASS | T10_PressureControl_SteadyState PASS |
| BPS-6.1-R02 | PASS | T10_PressureControl_SteadyState PASS |
| BPS-8.1-R01 | PASS | T10_PressureControl_SteadyState PASS, T16_DutySelection_LowerRunHours[lower=1] PASS, T16_DutySelection_LowerRunHours[lower=2] PASS |
| BPS-6.1-R03 | PASS | T11_ControllerOutputLimits PASS |
| BPS-6.2-R01 | KNOWN DEVIATION | T12_ConsumptionStep_PressureDeviation XFAIL |
| BPS-6.3-R01 | PASS | T13_PressureTransmitterFault_Fallback PASS |
| BPS-7.1-R01 | PASS | T14_HighPressureTrip_LatchedUntilAck PASS |
| BPS-7.1-R02 | PASS | T14_HighPressureTrip_LatchedUntilAck PASS |
| BPS-10-R01 | PASS | T14_HighPressureTrip_LatchedUntilAck PASS |
| BPS-10-R02 | PASS | T14_HighPressureTrip_LatchedUntilAck PASS |
| BPS-7.2-R01 | PASS | T15_LowPressureWarning PASS |
| BPS-8.1-R02 | PASS | T16_DutySelection_LowerRunHours[lower=1] PASS, T16_DutySelection_LowerRunHours[lower=2] PASS |
| BPS-8.1-R03 | PASS | T17_DutyAlternation PASS |
| BPS-8.2-R01 | PASS | T18_AssistPump PASS |
| BPS-8.2-R02 | PASS | T18_AssistPump PASS |
| BPS-8.3-R01 | PASS | T19_FeedbackLoss_Failover PASS |
| BPS-8.3-R02 | PASS | T19_FeedbackLoss_Failover PASS |
| BPS-8.3-R03 | PASS | T20_VfdFault PASS |
| BPS-8.4-R01 | PASS | T21_RunHoursAndStarts PASS |
| BPS-9-R01 | PASS | T22_SetpointSets PASS |
| BPS-9-R02 | PASS | T22_SetpointSets PASS |
5. Traceability
Requirements file requirements.json (SHA-256 d529cca3067947f243dfc1c2c6a89fcd4cd89940e7905617823c452b461cd525), specification ../spec/Pump_Station_Spec.md.
35requirements
100.0 %covered (35 direct, 0 by section)
0without tests
0tests without requirements
1KNOWN DEVIATION
1N/A
33PASS
Coverage gaps
| Requirements without tests (0) | none |
|---|---|
| Requirements whose tests are all N/A (1) | BPS-4.4-R01 |
| Requirements with known deviations (XFAIL) (1) | BPS-6.2-R01 |
| Tests without requirements (0) | none |
Matrix
| Requirement | Category / priority | Status | Tests (last result) | PLC objects |
|---|---|---|---|---|
| BPS-3.1-R01 The station shall have the operating modes Off, Manual and Auto, selected by the operator on the HMI. | function high | PASS | T01_ModeOff_AllOutputsOff PASS, T02_Manual_PumpsIndividually PASS | DB_Operator, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Station.Alarms.Common, DB_Station.Pressure_bar, DB_Station.Pump[1].RunHours, DB_Station.Pump[2].RunHours, H001_AlarmLamp, P1_Run, P1_RunFB, P1_SpeedRef, P2_Run … (17 tags) |
| BPS-3.1-R02 In mode Off all pump and valve outputs shall be switched off. | function high | PASS | T01_ModeOff_AllOutputsOff PASS | DB_Operator, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Station.Alarms.Common, DB_Station.Pressure_bar, DB_Station.Pump[1].RunHours, DB_Station.Pump[2].RunHours, H001_AlarmLamp, P1_Run, P1_RunFB, P1_SpeedRef, P2_Run … (17 tags) |
| BPS-3.2-R01 In mode Manual the operator shall start and stop each pump individually, and a started pump shall run at the manual speed setpoint. | function high | PASS | T02_Manual_PumpsIndividually PASS | DB_Operator, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Station.Alarms.Common, DB_Station.Pump[1].RunHours, DB_Station.Pump[2].RunHours, H001_AlarmLamp, P1_Run, P2_Run, P2_SpeedRef |
| BPS-3.2-R02 The dry-run protection, the high pressure trip and the emergency stop shall stay active in mode Manual. | safety high | PASS | T03_Manual_ProtectionsActive PASS | DB_Operator, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Station.Alarms.Common, DB_Station.Alarms.EStop, DB_Station.Alarms.HighPressure, DB_Station.Pump[1].RunHours, DB_Station.Pump[2].RunHours, H001_AlarmLamp, P1_Run |
| BPS-3.3-R01 When the emergency stop circuit opens, all pumps shall stop and the inlet valve shall close within 0.5 s. | safety high | PASS | T04_EStop_StopsAll_RestartAfterAck PASS | DB_Operator, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Station.Alarms.Common, DB_Station.Alarms.EStop, DB_Station.Pressure_bar, DB_Station.PumpsRunning, DB_Station.Pump[1].RunHours, DB_Station.Pump[2].RunHours, DB_Station.StationRun, H001_AlarmLamp, P1_Run … (18 tags) |
| BPS-3.3-R02 After the emergency stop circuit has been closed again, the pumps shall restart only after the operator has acknowledged the alarm. | safety high | PASS | T04_EStop_StopsAll_RestartAfterAck PASS | DB_Operator, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Station.Alarms.Common, DB_Station.Alarms.EStop, DB_Station.Pressure_bar, DB_Station.PumpsRunning, DB_Station.Pump[1].RunHours, DB_Station.Pump[2].RunHours, DB_Station.StationRun, H001_AlarmLamp, P1_Run … (18 tags) |
| BPS-4.1-R01 In modes Manual and Auto the inlet valve XV-101 shall open when the tank level falls below the refill start level (default 40 %). | setpoint high | PASS | T05_Refill_Hysteresis PASS | DB_Operator, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Station.Alarms.Common, DB_Station.Pressure_bar, DB_Station.Pump[1].RunHours, DB_Station.Pump[2].RunHours, H001_AlarmLamp, P1_RunFB, XV101_Open, XV101_ZSC, XV101_ZSO |
| BPS-4.1-R02 The inlet valve shall close when the tank level rises above the refill stop level (default 85 %). | setpoint high | PASS | T05_Refill_Hysteresis PASS | DB_Operator, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Station.Alarms.Common, DB_Station.Pressure_bar, DB_Station.Pump[1].RunHours, DB_Station.Pump[2].RunHours, H001_AlarmLamp, P1_RunFB, XV101_Open, XV101_ZSC, XV101_ZSO |
| BPS-4.2-R01 If the tank level exceeds the high level limit (default 95 %), the alarm A_HighLevel shall be raised and the inlet valve shall be closed. | alarm high | PASS | T06_HighLevel_ValveStuckOpen PASS | DB_Operator, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Station.Alarms.Common, DB_Station.Alarms.ValveFault, DB_Station.Pressure_bar, DB_Station.Pump[1].RunHours, DB_Station.Pump[2].RunHours, H001_AlarmLamp, P1_RunFB, XV101_Open, XV101_ZSC |
| BPS-4.3-R01 If the inlet valve does not reach the commanded end position within 15 s, the alarm A_ValveFault shall be raised. | alarm high | PASS | T06_HighLevel_ValveStuckOpen PASS | DB_Operator, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Station.Alarms.Common, DB_Station.Alarms.ValveFault, DB_Station.Pressure_bar, DB_Station.Pump[1].RunHours, DB_Station.Pump[2].RunHours, H001_AlarmLamp, P1_RunFB, XV101_Open, XV101_ZSC |
| BPS-4.4-R01 If the station is equipped with the optional mains pressure switch PS-100, a missing mains pressure shall raise the warning A_MainsLow. | alarm high | N/A | T07_MainsPressureSwitch N/A | DB_Station — DB_Station.Alarms.MainsLow |
| BPS-5.1-R01 If the tank level falls below the low-low level (default 10 %), all pumps shall stop within 1 s and the alarm A_LowLevel shall be raised. | alarm high | PASS | T08_DryRun_StopAndRestartHysteresis PASS | DB_Operator, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Station.Alarms.Common, DB_Station.Alarms.LowLevel, DB_Station.Pressure_bar, DB_Station.PumpsRunning, DB_Station.Pump[1].RunHours, DB_Station.Pump[2].RunHours, H001_AlarmLamp, P1_RunFB |
| BPS-5.1-R02 The pumps shall not restart before the tank level has risen above the low-low level plus the restart hysteresis (default 10 %). | setpoint high | PASS | T08_DryRun_StopAndRestartHysteresis PASS | DB_Operator, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Station.Alarms.Common, DB_Station.Alarms.LowLevel, DB_Station.Pressure_bar, DB_Station.PumpsRunning, DB_Station.Pump[1].RunHours, DB_Station.Pump[2].RunHours, H001_AlarmLamp, P1_RunFB |
| BPS-5.2-R01 If the level signal is out of range (wire break or short circuit), the alarm A_LevelSensor shall be raised, all pumps shall stop and the inlet valve shall close. | alarm high | PASS | T09_LevelTransmitterFault PASS | DB_Operator, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Station.Alarms.Common, DB_Station.Alarms.LevelSensor, DB_Station.Pressure_bar, DB_Station.PumpsRunning, DB_Station.Pump[1].RunHours, DB_Station.Pump[2].RunHours, DB_Station.StationRun, H001_AlarmLamp, P1_Run … (18 tags) |
| BPS-6.1-R01 In mode Auto the speed of the running pumps shall be controlled by a PI controller so that the header pressure follows the pressure setpoint (default 4.0 bar). | setpoint high | PASS | T10_PressureControl_SteadyState PASS | DB_Operator, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Station.Alarms.Common, DB_Station.AssistActive, DB_Station.DutyPump, DB_Station.Pressure_bar, DB_Station.PumpsRunning, DB_Station.Pump[1].RunHours, DB_Station.Pump[2].RunHours, H001_AlarmLamp, P1_Run … (17 tags) |
| BPS-6.1-R02 At constant consumption the header pressure shall stay within 0.2 bar of the setpoint. | setpoint high | PASS | T10_PressureControl_SteadyState PASS | DB_Operator, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Station.Alarms.Common, DB_Station.AssistActive, DB_Station.DutyPump, DB_Station.Pressure_bar, DB_Station.PumpsRunning, DB_Station.Pump[1].RunHours, DB_Station.Pump[2].RunHours, H001_AlarmLamp, P1_Run … (17 tags) |
| BPS-6.1-R03 The controller output shall be limited to the range from the minimum speed (default 30 %) to 100 %. | setpoint high | PASS | T11_ControllerOutputLimits PASS | DB_Operator, DB_Settings, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Settings.Active.Pressure_SP, DB_Station.Alarms.Common, DB_Station.Pressure_bar, DB_Station.Pump[1].RunHours, DB_Station.Pump[2].RunHours, DB_Station.Speed_pct, H001_AlarmLamp, P1_RunFB |
| BPS-6.2-R01 After a step of the consumption from 12 to 30 m3/h the header pressure shall not deviate more than 0.3 bar from the setpoint. | setpoint high | KNOWN DEVIATION | T12_ConsumptionStep_PressureDeviation XFAIL | DB_Operator, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Station.Alarms.Common, DB_Station.Pressure_bar, DB_Station.Pump[1].RunHours, DB_Station.Pump[2].RunHours, H001_AlarmLamp, P1_RunFB |
| BPS-6.3-R01 If the pressure signal is out of range, the alarm A_PressureSensor shall be raised and the running pumps shall continue at the fallback speed (default 70 %). | alarm high | PASS | T13_PressureTransmitterFault_Fallback PASS | DB_Operator, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Station.Alarms.Common, DB_Station.Alarms.PressureSensor, DB_Station.Pressure_bar, DB_Station.Pump[1].RunHours, DB_Station.Pump[2].RunHours, DB_Station.Speed_pct, H001_AlarmLamp, P1_RunFB, P1_SpeedRef |
| BPS-7.1-R01 If the header pressure exceeds the high pressure trip limit (default 6.0 bar), all pumps shall stop and the alarm A_HighPressure shall be raised. | alarm high | PASS | T14_HighPressureTrip_LatchedUntilAck PASS | DB_Operator, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Station.Alarms.Common, DB_Station.Alarms.HighPressure, DB_Station.Pressure_bar, DB_Station.PumpsRunning, DB_Station.Pump[1].RunHours, DB_Station.Pump[2].RunHours, DB_Station.StationRun, H001_AlarmLamp, P1_Run … (17 tags) |
| BPS-7.1-R02 A high pressure trip shall remain active until the operator acknowledges it on the HMI. | function high | PASS | T14_HighPressureTrip_LatchedUntilAck PASS | DB_Operator, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Station.Alarms.Common, DB_Station.Alarms.HighPressure, DB_Station.Pressure_bar, DB_Station.PumpsRunning, DB_Station.Pump[1].RunHours, DB_Station.Pump[2].RunHours, DB_Station.StationRun, H001_AlarmLamp, P1_Run … (17 tags) |
| BPS-7.2-R01 If the header pressure stays below the low pressure limit (default 2.0 bar) for longer than 10 s while a pump runs, the warning A_LowPressure shall be raised. | alarm high | PASS | T15_LowPressureWarning PASS | DB_Operator, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Station.Alarms.Common, DB_Station.Alarms.LowPressure, DB_Station.Pressure_bar, DB_Station.Pump[1].RunHours, DB_Station.Pump[2].RunHours, H001_AlarmLamp, P1_Run, P1_RunFB |
| BPS-8.1-R01 In mode Auto one pump shall run as duty pump while the other pump is the standby pump. | function high | PASS | T10_PressureControl_SteadyState PASS, T16_DutySelection_LowerRunHours[lower=1] PASS, T16_DutySelection_LowerRunHours[lower=2] PASS | DB_Operator, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Station.Alarms.Common, DB_Station.AssistActive, DB_Station.DutyPump, DB_Station.Pressure_bar, DB_Station.PumpsRunning, DB_Station.Pump[1].RunHours, DB_Station.Pump[2].RunHours, H001_AlarmLamp, P1_Run … (18 tags) |
| BPS-8.1-R02 At every start of the station the available pump with the lower run hours shall become the duty pump. | function high | PASS | T16_DutySelection_LowerRunHours[lower=1] PASS, T16_DutySelection_LowerRunHours[lower=2] PASS | DB_Operator, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Station.Alarms.Common, DB_Station.DutyPump, DB_Station.PumpsRunning, DB_Station.Pump[1].RunHours, DB_Station.Pump[2].RunHours, H001_AlarmLamp, P1_Run, P1_RunFB, P2_Run … (16 tags) |
| BPS-8.1-R03 The duty pump shall change over to the standby pump after the alternation time (default 24 h) of continuous running. | setpoint high | PASS | T17_DutyAlternation PASS | DB_Operator, DB_Settings, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Settings.Active.Alternation_Time, DB_Station.Alarms.Common, DB_Station.DutyPump, DB_Station.Pressure_bar, DB_Station.Pump[1].RunHours, DB_Station.Pump[2].RunHours, H001_AlarmLamp, P1_Run, P2_Run |
| BPS-8.2-R01 If the duty pump runs at 100 % speed for longer than the assist delay (default 10 s) and the header pressure is more than 0.3 bar below the setpoint, the standby pump shall be started as assist pump. | function high | PASS | T18_AssistPump PASS | DB_Operator, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Station.Alarms.Common, DB_Station.AssistActive, DB_Station.Pressure_bar, DB_Station.Pump[1].RunHours, DB_Station.Pump[2].RunHours, DB_Station.Speed_pct, H001_AlarmLamp, P1_Run, P1_RunFB … (16 tags) |
| BPS-8.2-R02 The assist pump shall be stopped when the common speed stays below the assist stop speed (default 80 %) for 10 s. | setpoint high | PASS | T18_AssistPump PASS | DB_Operator, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Station.Alarms.Common, DB_Station.AssistActive, DB_Station.Pressure_bar, DB_Station.Pump[1].RunHours, DB_Station.Pump[2].RunHours, DB_Station.Speed_pct, H001_AlarmLamp, P1_Run, P1_RunFB … (16 tags) |
| BPS-8.3-R01 If a pump does not confirm running within the feedback timeout (default 5 s) after its start command, the alarm A_Pn_NoFeedback shall be raised and the pump shall be marked as unavailable. | alarm high | PASS | T19_FeedbackLoss_Failover PASS | DB_Operator, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Station.Alarms.Common, DB_Station.DutyPump, DB_Station.Pressure_bar, DB_Station.Pump[1].Alm_NoFeedback, DB_Station.Pump[1].Available, DB_Station.Pump[1].RunHours, DB_Station.Pump[2].RunHours, H001_AlarmLamp, P1_Run … (18 tags) |
| BPS-8.3-R02 If the duty pump fails, the standby pump shall take over within 2 s after the failure has been detected. | alarm high | PASS | T19_FeedbackLoss_Failover PASS | DB_Operator, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Station.Alarms.Common, DB_Station.DutyPump, DB_Station.Pressure_bar, DB_Station.Pump[1].Alm_NoFeedback, DB_Station.Pump[1].Available, DB_Station.Pump[1].RunHours, DB_Station.Pump[2].RunHours, H001_AlarmLamp, P1_Run … (18 tags) |
| BPS-8.3-R03 A VFD fault signal shall stop the pump and raise the alarm A_Pn_VfdFault. | alarm high | PASS | T20_VfdFault PASS | DB_Operator, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Station.Alarms.Common, DB_Station.Pressure_bar, DB_Station.Pump[1].Alm_VfdFault, DB_Station.Pump[1].RunHours, DB_Station.Pump[2].RunHours, H001_AlarmLamp, P1_Run, P1_RunFB |
| BPS-8.4-R01 The PLC shall count the run hours and the number of starts of each pump. | function high | PASS | T21_RunHoursAndStarts PASS | DB_Operator, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Station.Alarms.Common, DB_Station.Pump[1].RunHours, DB_Station.Pump[1].Starts, DB_Station.Pump[2].RunHours, DB_Station.Pump[2].Starts, H001_AlarmLamp, P1_RunFB |
| BPS-9-R01 The station shall provide the three setpoint sets Day, Night and Maintenance, which the operator loads as active setpoints on the HMI. | function high | PASS | T22_SetpointSets PASS | DB_Operator, DB_Settings, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Settings.Active.Alternation_Time, DB_Settings.Active.Pressure_SP, DB_Settings.ActiveSet, DB_Station.Alarms.Common, DB_Station.Pressure_bar, DB_Station.Pump[1].RunHours, DB_Station.Pump[2].RunHours, H001_AlarmLamp, P1_Run … (16 tags) |
| BPS-9-R02 Loading a setpoint set shall not stop running pumps. | function high | PASS | T22_SetpointSets PASS | DB_Operator, DB_Settings, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Settings.Active.Alternation_Time, DB_Settings.Active.Pressure_SP, DB_Settings.ActiveSet, DB_Station.Alarms.Common, DB_Station.Pressure_bar, DB_Station.Pump[1].RunHours, DB_Station.Pump[2].RunHours, H001_AlarmLamp, P1_Run … (16 tags) |
| BPS-10-R01 Every alarm shall switch on the common alarm lamp H-001 until it is acknowledged. | alarm high | PASS | T14_HighPressureTrip_LatchedUntilAck PASS | DB_Operator, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Station.Alarms.Common, DB_Station.Alarms.HighPressure, DB_Station.Pressure_bar, DB_Station.PumpsRunning, DB_Station.Pump[1].RunHours, DB_Station.Pump[2].RunHours, DB_Station.StationRun, H001_AlarmLamp, P1_Run … (17 tags) |
| BPS-10-R02 All alarms shall be acknowledged with one acknowledge command on the HMI, and an alarm whose cause is still present shall stay active. | alarm high | PASS | T14_HighPressureTrip_LatchedUntilAck PASS | DB_Operator, DB_Station — DB_Operator.Ack, DB_Operator.ManP1, DB_Operator.ManP2, DB_Operator.Mode, DB_Operator.RecipeLoad, DB_Operator.RecipeSelect, DB_Station.Alarms.Common, DB_Station.Alarms.HighPressure, DB_Station.Pressure_bar, DB_Station.PumpsRunning, DB_Station.Pump[1].RunHours, DB_Station.Pump[2].RunHours, DB_Station.StationRun, H001_AlarmLamp, P1_Run … (17 tags) |
(§) = linked through a section reference (e.g. PREFIX-6.4) rather than the requirement id. PLC objects: data blocks of the tags, blocks named in the test source, then the tags written/checked by the tests.
6. Sign-off
| Role | Name | Date | Signature |
|---|---|---|---|
| Supplier | |||
| Customer |